beautypg.com

Troubleshooting, Blucube ™ condensing unit – Airedale BluCube 10-48kW User Manual

Page 68

background image





BluCube

Condensing Unit

68

Condensing Units

Installation and Maintenance Manual : 7222094 11/2013

Troubleshooting

FAULT

POSSIBLE CAUSE

REMEDY/ACTION

CRITICAL ALARMS:

Aux. Alarm

Auxiliary Trip.

Check operation of customer-added
alarm function.

Outdoor Fan Fault

Fan Trip.

Check and (if necessary) replace fan.

Coil Sensor Fault

Faulty Sensor.

Replace sensor.

No Cooling/Heating

Compressor Protection Delay.

Wait for a maximum of 10 minutes then
re-check.

Unit Will Not Start

No power.

Check power supply to the controller.

Wired incorrectly.

Check wire connections in accordance with
wiring diagram on control box lid.

Loose wires.

Check all wires, connections, terminals etc.

Compressor not operating

No power to compressor.

Check isolator, fuses, MCBs, contactor and
control circuit wiring.

Low pressure switch operated (if
fitted) (large or complete loss of
refrigerant charge).

Repair leak and recharge system - if
completely out evacuate before charging.

Condenser fan thermal trip open
circuit.

Investigate and correct.

Seized compressor.

Replace compressor - investigate oil
trapping and general installation.

Defective compressor motor.

Check winding resistances - replace
compressor. If burnt out follow burn out
procedure using suction line burn-out drier.

Noisy Compressor

Expansion valve malfunction
(abnormally cold suction Iine).

Ensure sensor is tight on suction and
superheat is correct (normally 5 to 6°C).
Replace power assembly or valve
as necessary.

Lack of oil.

Repair leaks if any, add oil if required but not
too much. Investigate pipe system and
trapping. If no oil still, drain compressor and
measure in correct quantity.

Broken or damaged compressor valve
reed (compressor knocking).

Replace compressor (possible other
symptom is that it will have high suction
pressure).

Worn or scored compressor bearing.
(excessive knocking).

Replace compressor.

Head Pressure too high/HP cut-
out operated

Condenser coil clogged or dirty.

Clean condenser.

Overcharge of refrigerant. Normally
troublesome in warm weather.

Remove excess refrigerant from system.

Air or other non-condensable gas
in system.

Evacuate system and re-charge with new
refrigerant.

Head pressure controller faulty.

Check fan speed controller - if
faulty - replace.

Fan not operating or operating
inefficiently.

Check motor - if faulty - replace.

Head pressure too low

Fan operating too fast in low
ambient conditions.

Check fan speed controller adjustment - if
faulty - replace.