Addressing the pco controller, Blucube ™ condensing unit – Airedale BluCube 10-48kW User Manual
Page 58

BluCube
™
Condensing Unit
58
Condensing Units
Installation and Maintenance Manual : 7222094 11/2013
Addressing the pCO Controller
The address of the controller can be configured by setting the display keypad to address 0 (zero).
To change the address of the pCO controller, press and hold the
+
buttons together and switch on the
controller. After the self test screen has been displayed, the pLAN address screen will be displayed.
Controller
Address 1
BluCube EEV
Driver
Address 9
Airedale REEV
Driver
Address 17
Remote Display
Address 32
The board address can also be changed be selecting Board Switch from the main menu:
The following screen will be displayed:
The unit number can be changed to another number on the network.