beautypg.com

Blucube ™ condensing unit, Condensing units, Refrigeration pipe sizing guide – Airedale BluCube 10-48kW User Manual

Page 26

background image





BluCube

Condensing Unit

26

Condensing Units

Installation and Maintenance Manual : 7222094 11/2013

Refrigeration Pipe Sizing Guide

Cooling Only

Equivalent Pipe Lengths with R410A

Outdoor

Unit

0-20m

Suction

20-40m

Suction

40-60m

Suction

60-80m

Suction

Connection Size

Liquid

Suction

Liquid

H

V

Liquid

H

V

Liquid

H

V

Liquid

H

V

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

CUR092V16-1CO-0

3/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

CUR092V20-1CO-0

1/2

1 1/8

1/2

1 3/8

7/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V25-1CO-0

1/2

1 3/8

1/2

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V29-1CO-0

1/2

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

CUR122V35-1CO-0

5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

CUR122V40-1CO-0

5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

CUR092V16-VCO-0

3/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

1/2

1 1/8

7/8

CUR092V20-VCO-0

1/2

1 1/8

1/2

1 3/8

1 1/8

1/2

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V25-VCO-0

1/2

1 3/8

1/2

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

5/8

1 3/8

1 1/8

CUR092V29-VCO-0

1/2

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

5/8

1 5/8

1 3/8

CUR122V35-VCO-0

5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

3/4

1 5/8

1 3/8

CUR122V40-VCO-0

5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

3/4

1 5/8

1 5/8

7/8

1 5/8

1 5/8

Heat Pump

Equivalent Pipe Lengths with R410A

Outdoor

Unit

Connection Size

0-

20

m

Suction /

Disch

20-

40m

Suction /

Disch

40-

60m

Suction /

Disch

60-

80m

Suction /

Disch

Liquid

Suction

Disch

Liq
uid

H

V

Liquid

H

V

Liquid

H

V

Liquid

H

V

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

(3)

(1)

(2)

CUR092V16-1HP-
0

3/8

1/2

1/2

3/4

1/2

1/2

3/4

5/8

1/2

3/4

5/8

1/2

3/4

5/8

CUR092V20-1HP-
0

3/8

5/8

1/2

7/8

5/8

5/8

7/8

5/8

5/8

7/8

5/8

5/8

7/8

5/8

CUR092V25-1HP-
0

1/2

7/8

1/2

1 1/8

5/8

5/8

1 1/8

3/4

5/8

1 1/8

3/4

5/8

1 1/8

3/4

CUR092V29-1HP-
0

1/2

7/8

5/8

1 1/8

3/4

5/8

1 1/8

3/4

3/4

1 1/8

3/4

3/4

1 1/8

3/4

CUR122V35-1HP-
0

1/2

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

CUR122V40-1HP-
0

5/8

1 1/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

CUR092V16-VHP-
0

3/8

1/2

1/2

7/8

1/2

1/2

7/8

1/2

1/2

7/8

1/2

1/2

7/8

1/2

CUR092V20-VHP-
0

3/8

5/8

1/2

7/8

5/8

1/2

7/8

5/8

5/8

7/8

5/8

5/8

7/8

5/8

CUR092V25-VHP-
0

1/2

7/8

1/2

1 1/8

5/8

5/8

1 1/8

5/8

5/8

1 1/8

5/8

5/8

1 1/8

5/8

CUR092V29-VHP-
0

1/2

7/8

5/8

1 1/8

3/4

5/8

1 1/8

3/4

5/8

1 1/8

3/4

5/8

1 1/8

3/4

CUR122V35-VHP-
0

1/2

7/8

3/4

1 3/8

3/4

3/4

1 3/8

3/4

3/4

1 3/8

3/4

3/4

1 3/8

3/4

CUR122V40-VHP-
0

5/8

1 1/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

3/4

1 3/8

7/8

7/8

1 3/8

7/8

(1) For interconnecting pipework with a predominantly horizontal layout.

(2) For interconnecting pipework with a predominantly vertical layout.

(3) Careful pipework selection must be done if the liquid line rises. Additional system sub cooling may be required to overcome friction losses.


All pipe sizes have been calculated based on a nominal condition 7°C evaporating and 50°C condensing

Suction and discharge double risers may be required for modulating capacity units at part load.