Condensing units blucube, Condensing units – Airedale BluCube 10-48kW User Manual
Page 31
![background image](/manuals/370958/31/background.png)
Condensing Units
BluCube
™
Condensing Units
31
Installation and Maintenance Manual 7222094: 11/2013
Mechanical Data Cooling Only Fixed Capacities Continued
CUR092V29-1CO-0
CUR122V35-1CO-0
CUR122V40-1CO-0
Capacity
Nominal Cooling Capacity
(1)
kW
28.6
38.8
43.4
Capacity Steps
1
1
1
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1736
1222 x 764 x 1736
1222 x 764 x 1736
Masses
– Machine / Operating
(3)
kg
241
292
296
Construction
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint
– Light Grey (RAL 7035)
Material/Colour
Condenser
Rifled Copper Tube/Louvered Hydrophilic Coated Aluminium Fins
Fan Motor
Axial
Motor Type
AC 1ph
AC 3ph
AC 3ph
Quantity x Motor Size
kW
1 x 0.6
1 x 1.97
1 x 1.97
Diameter
mm
630
630
630
Maximum Fan Speed
RPM
860
1330
1330
Maximum Airflow
m³/s
2.0
3.5
3.5
Compressor
Compressor Type
Fixed Capacity Scroll
Quantity
1
1
1
Oil Charge Volume
l
3.3
3.3
3.6
Oil Type
Polyolester
Refrigeration
Single Circuit - 2 pipe configuration
Refrigerant control and type
Optional REEV package
Refrigerant type
R410A
Holding Charge
Inert Gas
Coil Volume
l
9.9
12.4
12.4
Refrigerant Charge
(4)
kg
5.8
7.3
7.4
Connections
Liquid (sweat)
in
1/2
5/8
5/8
Suction (sweat)
in
1 3/8
1 3/8
1 5/8
Optional Extras
EC Fan
Quantity x Motor Size
kW
1 x 0.72
1 x 1.85
1 x 1.85
Diameter
mm
630
630
630
Maximum Fan Speed
RPM
1000
1230
1230
Maximum Airflow
m³/s
2.3
3.5
3.5
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1750
1222 x 764 x 1750
1222 x 764 x 1750
Masses
– Machine / Operating
(3)
kg
233
284
287
Short Case Axial Fan
Designed to 75Pa ESP
Quantity x Motor Size
kW
1 x 1.4
N/A
N/A
Diameter
mm
560
N/A
N/A
Maximum Fan Speed
RPM
1330
N/A
N/A
Maximum Airflow
m³/s
2.8
N/A
N/A
Dimensions
– W x D x H
(2)
mm
922 x 764 x 1753
N/A
N/A
Masses
– Machine / Operating
(3)
kg
247
N/A
N/A
REEV Selection
E²V
– 35
E²V - 45
E²V - 45
(1) Evaporating temperature 7°C, Ambient 35°C with an AC fan matched with a REEV package
(2) Overall dimensions for clearance
(3) Unit mass excludes a refrigerant charge
(4) For guidance only