beautypg.com

Heat pump cooling fixed capacities, Condensing units blucube, Condensing units – Airedale BluCube 10-48kW User Manual

Page 41

background image







Condensing Units

BluCube

Condensing Units

41

Installation and Maintenance Manual 7222094: 11/2013

Heat Pump Cooling Fixed Capacities

Summer Ambient (°C)

25

30

35

40

45

Unit

Evap

Temp

(°C)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

CUR092V16-1HP-0

-5

10.3

3.9

10.3

3.8

9.8

4.2

9.2

4.6

8.5

5.0

0

12.4

3.9

12.2

3.9

11.6

4.3

11.0

4.7

10.3

5.2

5

14.8

3.9

14.4

4.0

13.7

4.4

13.0

4.8

12.2

5.3

7

15.9

3.8

15.4

4.0

14.6

4.4

13.8

4.8

13.0

5.3

10

17.6

3.7

16.9

4.0

16.0

4.4

15.2

4.9

14.3

5.3

CUR092V20-1HP-0

-5

15.8

5.5

15.1

5.8

14.3

6.3

13.3

6.8

N/A

N/A

0

18.7

5.5

17.9

6.0

17.0

6.5

15.9

7.0

14.8

7.6

5

21.9

5.7

20.9

6.1

19.8

6.6

18.7

7.2

17.5

7.7

7

23.3

5.7

22.2

6.2

21.1

6.7

19.9

7.2

18.7

7.8

10

25.4

5.8

24.2

6.3

23.0

6.8

21.8

7.3

21.1

6.7

CUR092V25-1HP-0

-5

20.3

7.0

19.3

7.7

18.3

8.4

17.1

9.1

N/A

N/A

0

24.0

7.4

22.8

8.0

21.5

8.7

20.1

9.5

N/A

N/A

5

28.1

7.8

26.6

8.4

25.0

9.1

23.3

9.9

N/A

N/A

7

29.8

8.0

28.2

8.6

26.5

9.3

24.6

10.1

N/A

N/A

10

32.4

8.2

30.6

8.9

28.8

9.6

26.7

10.3

N/A

N/A

CUR092V29-1HP-0

-5

22.5

8.0

21.2

8.7

19.9

9.5

28.7

10.6

N/A

N/A

0

26.5

8.4

25.0

9.1

23.4

10.0

21.6

10.9

N/A

N/A

5

30.8

8.9

29.0

9.6

27.1

10.4

25.1

11.4

N/A

N/A

7

32.6

9.0

30.7

9.8

28.7

10.6

26.6

11.6

N/A

N/A

10

35.4

9.3

33.3

10.1

31.1

11.0

28.7

10.6

N/A

N/A

CUR122V35-1HP-0

-5

30.5

11.8

29.0

12.9

27.2

13.9

25.3

15.1

N/A

N/A

0

36.1

12.3

34.2

13.2

32.1

14.3

29.8

15.5

N/A

N/A

5

42.1

12.7

39.9

13.7

37.4

14.8

34.8

15.9

31.9

17.3

7

44.6

12.9

42.3

13.9

39.7

14.9

36.9

16.1

33.9

17.5

10

48.6

13.2

46.0

14.2

43.2

15.3

40.2

16.4

39.7

14.9

CUR122V40-1HP-0

-5

34.5

13.5

32.7

14.5

30.7

15.6

28.6

16.8

N/A

N/A

0

40.4

14.1

38.3

15.1

36.0

16.2

33.5

17.4

N/A

N/A

5

46.9

14.8

44.4

15.7

41.7

16.8

38.8

18.1

N/A

N/A

7

49.6

15.0

47.0

16.0

44.1

17.1

41.0

18.4

N/A

N/A

10

53.9

15.4

51.0

16.5

47.8

17.6

44.5

18.8

N/A

N/A

Notes:
1

Output kW refers to the compressor duty.

2