beautypg.com

Technical data 75, Power supply 75, Technical data – West Control Solutions KS 92-1 Programmer manual User Manual

Page 75

background image

Nominal voltage

24 V DC external

Current sink (IEC 1131 type 1)
Logic “0”

-3...5 V

Logic “1”

15...30 V

Current requirement

approx.. 5 mA

TRANSMITTER SUPPLY U

T

(OPTION)

Power:

22 mA /

³ 18 V

As analog outputs OUT3 or OUT4 and trans-
mitter supply U

T

are connected to different volt-

age potentials, an external galvanic connection
between OUT3/4 and U

T

is not permissible with

analog outputs.

GALVANIC ISOLATION

Safety isolation
Function isolation

OUTPUTS

RELAY OUTPUTS OU

T1...OUT4

Contact type

:

potential-free changeover
contact

Max.contact rating

:

500 VA, 250 V, 2A at 48...62 Hz,
resistive load

Min. contact rating

:

6V, 1mA DC

Number of electical
switching cycles

:

for I = 1A/2A:

≥ 800.000 /

500.000 (at ~ 250V (resistive
load)

Note:
If the relays operate external contactors, these
must be fitted with RC sn

ubber circuits to man-

ufacturer specifications to prevent excessive
switch-off voltage peaks.

OUT3, 4 AS UNIVERSAL OUTPUT

Galvanically isolated from the inputs.

Freely scalable resolution:

11 bits

Current output

0/4...20 mA configurable.
Signal range:

0...approx.22mA

Max. load:

£ 500 W

Load effect:

no effect

Resolution:

£ 22 mA (0,1%)

Accuracy

£ 40 mA (0,2%)

Voltage output

0/2...10V configurable
Signal range:

0...11 V

Min. load:

≥ 2 kW

Load effect:

no effect

Resolution:

£11 mV (0,1%)

Accuracy

£ 20 mV (0,2%)

OUT3, 4 used as transmitter supply

Output power:

22 mA /

³ 13 V

OUT3, 4 used as logic output

Load

£ 500 W

0/

£ 20 mA

Load > 500

W

0/> 13 V

OUTPUTS OUT5/6 (OPTION)

Galvanically isolated opto-coupler outputs.
Grounded load: common positive voltage.
Output rating: 18...32 VDC;

≤ 70 mA

Internal voltage drop:

≤ 1 V with I

max

Protective circuit: built-in against short circuit,
overload, reversed polarity (free-wheel diode
for relay loads).

POWER SUPPLY

Dependent of order:

AC SUPPLY

Voltage:

90...250 V AC

Frequency:

48...62 Hz

Power consumption

approx. 10 VA

Technical data

KS 90-1

p / KS 92-1

p

75

Process value input INP1

Mains supply

Supplementary input INP2
Optional input INP3
Digital input di1, di2

Relay OUT1

RS422/485 interface

Relay OUT2

Digital inputs di2, 3

Relay OUT3

Universal output OUT3

Relay OUT4

Universal output OUT4
Transmitter supply U

T

OUT5, OUT6

This manual is related to the following products: