5 self-tuning 15, 5 self-tuning – West Control Solutions KS 92-1 Programmer manual User Manual

Page 15

background image

Self-tuning heating (

ADA.H) and cooling ( ADA.C) error status:

3.5 Self-tuning

For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt,
whereby the process characteristics are used to calculate the parameters for fast
line-out to the set-point without overshoot.

The following parameters are optimized when self-tuning:
Parameter set 1:

Pb1

- Proportional band 1 (heating) in engineering units [e.g. °C]

ti1

- Integral time 1 (heating) in [s]r only, unless set to

OFF

td1

- Derivative time 1 (heating) in [s]r only, unless set to

OFF

t1

- Minimum cycle time 1 (heating) in [s]r only, unless Adt0 was

set to “no self-tuning” during configuration by means of
BlueControl

®

.

Pb2

- Proportional band 2 (cooling) in engineering units [e.g. °C]

ti2

- Integral time 2 (cooling) in [s]r only, unless set to

OFF

td2

- Derivative time 2 (cooling) in [s]r only, unless set to

OFF

t2

- Minimum cycle time 2 (cooling) in [s] r only, unless Adt0 was

set

to “no self-tuning” during configuration by means of

BlueControl

®

.

Parameter set 2: analogous to parameter set 1 (see page )

Operation

KS 90-1

p / KS 92-1

p

15

Self-tuning

Error

status

Description

Behaviour

0

No error

3

Faulty control ac-

tion

Re-configure controller (inverse i direct)

4

No response of

process variable

The control loop is perhaps not closed: check sensor, connections

and process

5

Low reversal point Increase ( ADA.H) max. output limiting Y.Hi or decrease (

ADA.C) min. output limiting Y.Lo

6

Danger of excee-

ded set-point (pa-

rameter

determined)

If necessary, increase (inverse) or reduce (direct) set-point

7

Output step chan-

ge too small (dy >

5%)

Increase ( ADA.H) max. output limiting Y.Hi or reduce ( ADA.C)

min. output limiting Y.Lo

8

Set-point reserve

too small

Acknowledgment of this error message leads to switch-over to auto-

matic mode.If self-tuning shall be continued,

increase set-point (invers), reduce set-point (direct)

or decrease set-point range

(r

PArA / SEtp / SP.LO and SP.Hi )

9

Impulse tuning fai-

led

The control loop is perhaps not closed: check sensor, connections

and process

This manual is related to the following products: