Configuration level – West Control Solutions KS 92-1 Programmer manual User Manual
Page 41
g
Resetting the controller configuration to factory setting (Default)
r chapter (page )
+
BlueControl - the engineering tool for the BluePort
â
controller series
3 engineering tools with different functionality facilitating KS90-1
configuration and parameter setting are available (see chapter 10: Accessory
equipment with ordering information).
In addition to configuration and parameter setting, the engineering tools are
used for data acquisition and offer long-term storage and print functions. The
engineering tools are connected to KS90-1 via the front-panel interface
"BluePort
â
" by means of PC (Windows 95 / 98 / NT) and a PC adaptor.
Description BlueControl: see chapter 9: BlueControl (page 72).
Configuration level
KS 90-1
p / KS 92-1
p
41
Configuration parameters
Lin
(only visible with BlueControl
â
Name
Value range Description
Default
Lin
Linearization for inputs INP1 or INP3
Access to this table is always with selection special thermocouple
for
InP.1 or InP.3or with setting S.Lin = 1: special linea-
rization for linearization.
Default: KTY 11-6 (0...4,5 kOhm)
U.LinT
Unit of linearizationtable
0
0
No unit
1
In Celsius [°C]
2
In Fahrenheit [°C]
In.1
-999.0..99999
Input value 1
The signal is in [µV] or in [[] dependent of input type
1036
Ou.1
0,001...9999 Output value 1 Signal assigned to
In.1
-49,94
In.2
-999.0..9999
9
Input value 2
The signal is in [µV] or in [[] dependent of input type
1150
Ou.2
0,001...9999 Output value 2 Signal assigned to
In.2
-38,94
:
:
:
:
:
:
:
:
In.16
-999.0..9999
9
Input value 16
The signal is in [µV] or in [[] dependent of input type
4470
Ou.16
0,001...9999 Output value 16 Signal assigned to
In.16
150,0