6
Calibration level
Measured value correction (
CAL)
is only visible if
ConF / InP.1 / Corr = 1
or
2 is chosen.
The measured value can be matched in the calibration menu (
CAL). Two meth-
ods are available:
Offset correction
(
ConF/ InP.1 / Corr =1 ):
w possible on-line at the
process
2-point correction
(
ConF/ InP.1 / Corr = 2 ):
w is possible off-line with
process value simulator
Calibration level
56
KS 90-1
p / KS 92-1
p
X
standard setting
offset correction
InL.1
OuL.1
new
display
OuL.1
old
X
standard setting
2-point correction
InL.1
InH.1
OuL.1
new
OuH.1
new
display
OuH.1
old
OuL.1
old