Configuration 34, Out.1, Out.2 – West Control Solutions KS 92-1 Programmer manual User Manual
Page 34: Configuration level
Configuration level
Configuration parameters
34
KS 90-1
p / KS 92-1
p
Name
Value range Description
Default
3
measured value INP1
4
measured value INP2
5
measured value INP3
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal setpoint) =
deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process va-
lue function “mean value” for recognizing aged thermocouples
11
Control deviation (=relative alarm) with suppression after
start-up and setpoint change without time limit
After switch-on or setpoint change, alarm output is suppressed,
until the process was within the limits once.
HC.AL
Alarm heat current function (INP2)
0
0
switched off
1
Overload short circuit monitoring
2
Break and short circuit monitoring
LP.AL
Monitoring of control loop interruption for heating
0
0
switched off / inactive
1
Active. If
ti1=0 LOOP alarm is inactive!
Loop alarm active. A loop break is recognized, with Y=100% if
2 x ti passes by without appropriate reaction of process value
Hour
OFF...999999
Operating hours (only visible with BlueControl
â
!)
OFF
Swit
OFF...999999
Output switching cycles (only visible with BlueControl
â
!)
OFF
q
Out.1
and
Out.2
Name
Value range Description
Default
O.Act
Method of operation of output OUT1
0
0
direct / normally open
1
inverse / normally closed
Y.1
Y.2
Controller output Y1/Y2
1
0
not active
1
active
Lim.1
Lim.2
Lim.3
Limit 1/2/3 signal
0
0
not active
1
active
LP.AL
Interruption alarm signal (LOOP)
0
0
not active
1
active
HC.AL
Heat current alarm signal
0
0
not active
1
active
HC.SC
Solid state relay (SSR) short circuit signal
0
0
not active
1
active
P.EnD
Message "Programm end"
0
0
not active
1
active