Configuration level – West Control Solutions KS 92-1 Programmer manual User Manual
Page 33
Configuration level
KS 90-1
p / KS 92-1
p
33
Configuration parameters
Name
Value range Description
Default
20
Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring resis-
tance + lead resistance ß160 [ )
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 850.0 °C)
23
special 0...4500 Ohm (preset to KTY11-6)
24
special 0...450 Ohm
30
0...20mA / 4...20mA 1
41
special -2,5...115 mV 1
42
special -25...115 0mV 1
50
potentiometer 0...160 Ohm 1
51
potentiometer 0...450 Ohm 1
52
potentiometer 0...1600 Ohm 1
53
potentiometer 0...4500 Ohm 1
Corr
Measured value correction / scaling
(only at
S.tYP = 23,24,30,41 and 42 adjustable)
0
0
Without scaling
1
Offset correction (offset entry is at controller
CALlevel)
2
2-point correction (calibration is at controller
CALlevel)
3
Scaling (at
PArA level)
4
Automatic calibration of position-feedback-potentiometer
In.F
-1999...9999
Alternative value for error at INP3
If a value is adjusted, this value is used for display and calculation
in case of error (e.g. FAIL).
a Before activating a substitute value, the effect in the
control loop should be considered!
OFF
fAI3
Forcing INP3 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
1 with current and voltage input signals, scaling is required (see chapter 5.3)
q
Lim
Name
Value range Description
Default
Fnc.1
Fnc.2
Fnc.3
Function of limit 1/2/3
1
0
switched off
1
measured value monitoring
2
Measured value monitoring + alarm latch. A latched limit value
can be reset via error list or via a digital input, or by pressing key
Ò or
è
(->
LOGI/ Err.r)
3
signal change (change/minute)
4
signal change and storage (change/minute)
Src.1
Src.2
Src.3
Source of Limit 1/2/3
1
0
process value
1
control deviation xw (process value - set-point)
2
Control deviation Xw (=relative alarm) with suppression after
start-up and setpoint change
After switch-on or setpoint change, alarm output is suppressed,
until the process value was within the limits once. At the latest af-
ter elapse of time 10
ti1 the alarm is activated. (ti1 = inte-
gral time 1; parameter r
Cntr)
ti1 switched off (ti1 = 0) is considered as Î , i.e. the alarm
is not activated, until the process value was within the limits once.