Configuration level – West Control Solutions KS 92-1 Programmer manual User Manual

Page 33

background image

Configuration level

KS 90-1

p / KS 92-1

p

33

Configuration parameters

Name

Value range Description

Default

20

Pt100 (-200.0 ... 100,0 °C)

( -200,0 ... 150,0°C with reduced lead resistance: measuring resis-

tance + lead resistance ß160 [ )

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0 ... 850.0 °C)

23

special 0...4500 Ohm (preset to KTY11-6)

24

special 0...450 Ohm

30

0...20mA / 4...20mA 1

41

special -2,5...115 mV 1

42

special -25...115 0mV 1

50

potentiometer 0...160 Ohm 1

51

potentiometer 0...450 Ohm 1

52

potentiometer 0...1600 Ohm 1

53

potentiometer 0...4500 Ohm 1

Corr

Measured value correction / scaling

(only at

S.tYP = 23,24,30,41 and 42 adjustable)

0

0

Without scaling

1

Offset correction (offset entry is at controller

CALlevel)

2

2-point correction (calibration is at controller

CALlevel)

3

Scaling (at

PArA level)

4

Automatic calibration of position-feedback-potentiometer

In.F

-1999...9999

Alternative value for error at INP3

If a value is adjusted, this value is used for display and calculation

in case of error (e.g. FAIL).

a Before activating a substitute value, the effect in the

control loop should be considered!

OFF

fAI3

Forcing INP3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

1 with current and voltage input signals, scaling is required (see chapter 5.3)

q

Lim

Name

Value range Description

Default

Fnc.1
Fnc.2
Fnc.3

Function of limit 1/2/3

1

0

switched off

1

measured value monitoring

2

Measured value monitoring + alarm latch. A latched limit value

can be reset via error list or via a digital input, or by pressing key

Ò or

è

(->

LOGI/ Err.r)

3

signal change (change/minute)

4

signal change and storage (change/minute)

Src.1
Src.2
Src.3

Source of Limit 1/2/3

1

0

process value

1

control deviation xw (process value - set-point)

2

Control deviation Xw (=relative alarm) with suppression after

start-up and setpoint change
After switch-on or setpoint change, alarm output is suppressed,

until the process value was within the limits once. At the latest af-

ter elapse of time 10

ti1 the alarm is activated. (ti1 = inte-

gral time 1; parameter r

Cntr)

ti1 switched off (ti1 = 0) is considered as Î , i.e. the alarm

is not activated, until the process value was within the limits once.