3 programmer description 62, 1 general 62, 3 programmer description – West Control Solutions KS 92-1 Programmer manual User Manual
Page 62: Programmer level
7.3 Programmer description
7.3.1 General
A survey of the most important features:
w Programs: 8 or 16 (dependent of order)
w Control outputs: 4
w Segments:16 per program
w Segment types: - ramp (set-point and time)
- ramp (set-point and gradient)
- hold segment (holding time)
- step segment (with alarm suppression)
- end segment
All segment types can be combined with ”Wait at the end and call operator”
w Time unit: configurable in hours:minutes or minutes:seconds
w Maximum segment duration:9999 hours = 1 year 51 days
w Maximum program duration:16 x 9999 hours = > 18 years
w Gradient:0,01°C/h ( /min) to 9999°C/h ( /min)
w Program name: 8 characters, adjustable via BlueControl software
w Bandwidth control: bandwidth high and low (b.Lo,b.Hi) limits defininable for
each program