3.8 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs. Gen-
erally, outputs
OuT.1... OuT.6 can be used each for alarm signalling. If more
than one signal is linked to one output the signals are OR linked. Each of the 3
limit values
Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min),
which can be switched off individually (parameter = “
OFF”). Switching differ-
ence
HYS.x and delay dEl.x of each limit value is adjustable.
1: normally closed ( ConF/ Out.x / O.Act=1 ) (see examples in the drawing)
2: normally open ( ConF/ Out.x / O.Act= 0 ) (inverted output relay action)
Operation
KS 90-1
p / KS 92-1
p
25
Alarm handling
L.1
LED
HYS.1
InL.1
InH.1
2
1
H.1 = OFF
L.1
LED
HYS.1
InL.1
InH.1
SP
2
1
H.1 = OFF
H.1
LED
HYS.1
InL.1
InH.1
2
1
Ü Operaing principle absolut alarm
L.1 = OFF
LED
HYS.1
H.1
InL.1
InH.1
SP
2
1
* Operating principle relative alarm
L.1 = OFF
L.1
LED
LED
HYS.1
HYS.1
H.1
InL.1
InH.1
SP
2
2
1
L.1
LED
LED
HYS.1
HYS.1
H.1
InL.1
InH.1
2
2
1