Configuration 31, Inp.2, Configuration level – West Control Solutions KS 92-1 Programmer manual User Manual
Page 31
Configuration level
KS 90-1
p / KS 92-1
p
31
Configuration parameters
Name
Value range Description
Default
20
Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring resis-
tance + lead resistance ß160 [ )
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 850.0 °C)
23
special 0...4500 Ohm (preset to KTY11-6)
24
special 0...450 Ohm
30
0...20mA / 4...20mA 1
40
0...10V / 2...10V 1
41
special -2,5...115 mV 1
42
special -25...1150 mV 1
50
potentiometer 0...160 Ohm 1
51
potentiometer 0...450 Ohm 1
52
potentiometer 0...1600 Ohm 1
53
potentiometer 0...4500 Ohm 1
S.Lin
Linearization (only at
S.tYP=23(KTY11-6), 24 (0...450W),30
(0..20mA), 40 (0..10V), 41 (0...100mV) and 42 (special -25...1150 mV))
0
0
none
1
Linearization to specification. Creation of linearization table with
BlueControl (engineering tool) possible. The characteristic for
KTY 11-6 temperature sensors is preset.
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction ((controller offset adjustment is at
CALlevel) )
2
2-point correction (calibration is at the controller
CALlevel )
3
Scaling (at
PArA level)
In.f
-1999...9999
Alternative value for error at INP1
If a value is adjusted, this value is used for display and calculation
in case of error (e.g. FAIL).
a
Before activating a substitute value, the effect in the
control loop should be considered!
OFF
fAI1
Forcing INP1 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
1 with current and voltage input signals, scaling is required (see chapter 5.3)
q
InP.2
Name
Value range Description
Default
I.Fnc
Function selection of INP2
1
0
no function (subsequent input data are skipped)
1
heating current input
2
external set-point (
SP.E)
3
Yp input
4
Second process value X2
5
External positioning value Y.E (switch-over r
LOGI / Y.E)
6
no controller input (e.g. transmitter input instead)
7
Process value x1