5.3 Input scaling
When using current, voltage or resistance signals as input variables for
InP.1,
InP.2 or/and InP.3 scaling of input and display values at parameter setting
level is required. Specification of the input value for lower and higher scaling
point is in the relevant electrical unit (mA/V/
W).
5.3.1 Input
Inp.1 and InP.3
g
Parameters
InL.x , OuL.x, InH.x and OuH.x are only visible if
ConF / InP.x / Corr = 3 is chosen.
In addition to these settings,
InL.x and InH.x can be adjusted in the range
(0...20mA / 0...10V/
W) determined by selection of S.tYP .
a
For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for
InL.x and OuL.x and for InH.x and
OuH.x must have the same value.
g
Input scaling changes at calibration level (r page 56) are displayed by input
scaling at parameter setting level. After calibration reset (
OFF), the scaling
parameters are reset to default.
5.3.2 Input
InP.2
In addition to these settings,
InL.2 and InH.2 can be adjusted in the range
(0...20/ 50mA/
W) determined by selection of S.tYP.
Parameter setting level
KS 90-1
p / KS 92-1
p
55
Input scaling
mA/V
phys.
quantity
mA / V
phys. quantity
OuH.x
OuL.x
InH.x
InL.x
S.tYP
Input signal
InL.x
OuL.x
InH.x
OuH.x
30 (0...20mA)
0 … 20 mA
0
any
20
any
4 … 20 mA
4
any
20
any
40 (0...10V)
0 … 10 V
0
any
10
any
2 … 10 V
2
any
10
any
S.tYP
Input signal
InL.2
OuL.2
InH.2
OuH.2
30
0 … 20 mA
0
any
20
any
31
0 … 50 mA
0
any
50
any