Configuration 35, Out.3, Out.4 – West Control Solutions KS 92-1 Programmer manual User Manual
Page 35: Configuration level
Configuration level
KS 90-1
p / KS 92-1
p
35
Configuration parameters
Name
Value range Description
Default
FAi.1
FAi.2
FAi.3
INP1/ INP2 / INP3 error signal
0
0
not active
1
active
dP.Er
PROFIBUS error
0
0
not active
1
active: Profibus trouble, no communication with this
instrument.
Prg.1
Prg.2
Prg.3
Prg.4
Programmer Control track 1/2/3/4
0
not active
1
active
CAll
Operator call
0
not active
1
active
fOut
Forcing OUT1 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
Configuration parameters Out.2 as Out.1 except for: Default
Y.1 = 0 Y.2 = 1
q
Out.3
and
Out.4
Name
Value range Description
Default
O.tYP
Signal type selection OUT3
0
0
relay / logic (only visible with current/logic voltage)
1
0 ... 20 mA continuous (only visible with current/logic/voltage)
2
4 ... 20 mA continuous (only visible with current/logic/voltage)
3
0...10 V continuous (only visible with current/logic/voltage)
4
2...10 V continuous (only visible with current/logic/voltage)
5
transmitter supply (only visible without OPTION)
O.Act
Method of operation of output OUT3 (only visible when O.TYP=0)
1
0
direct / normally open
1
inverse / normally closed
Y.1
Y.2
Controller output Y1/ Y2 (only visible when O.TYP=0)
0
0
not active
1
active
Lim.1
Lim.2
Lim.3
Limit 1/2/3 signal (only visible when O.TYP=0)
1
0
not active
1
active
LP.AL
Interruption alarm signal (LOOP) (only visible when O.TYP=0)
0
0
not active
1
active
HC.AL
Heating current alarm signal (only visible when O.TYP=0)
0
0
not active
1
active
HC.SC
Solid state relay (SSR) short circuit signal (only visible when O.TYP=0)
0
0
not active
1
active
P.EnD
Message "Programm end"
0
0
not active
1
active