2 parameters 53, Parameters 53 - 54, Cntr – West Control Solutions KS 92-1 Programmer manual User Manual
Page 53: Par.2, Setp, 2 parameters, Second parameterset, Parameter setting level
5.2 Parameters
Parameter setting level
KS 90-1
p / KS 92-1
p
53
Parameters
q
Cntr
Name
Value range Description
Default
Pb1
1...9999 1
Proportional band 1 (heating) in phys. dimensions (e.g. °C)
100
Pb2
1...9999 1
Proportional band 2 (cooling) in phys. dimensions (e.g. °C)
100
ti1
0,1...9999
Integral action time 1 (heating) [s]
180
ti2
0,1...9999
Integral action time 2 (cooling) [s]
180
td1
0,1...9999
Derivative action time 1 (heating) [s]
180
td2
0,1...9999
Derivative action time 2 (cooling) [s]
180
t1
0,4...9999
Minimal cycle time 1 (heating) [s]. The minimum impulse is 1/4 x t1
10
t2
0,4...9999
Minimal cycle time 2 (heating) [s]. The minimum impulse is 1/4 x t2
10
SH
0...9999
Neutral zone or switching differential for on-off control [phys. dimensions)
2
Hys.l
0...9999
Switching difference Low signaller [engineering unit]
1
Hys.H
0...9999
Switching difference High signaller [engineering unit]
1
d.SP
-1999...9999
Trigger point seperation for additional contact
D/Y/Off[phys.dimensions]
100
tP
0,1...9999
Minimum impulse [s]
OFF
tt
3...9999
Motor travel time [s]
60
Y.Lo
-120...120
Lower output limit [%]
0
Y.Hi
-120...120
Upper output limit [%]
100
Y2
-100...100
2. correcting variable
0
Y.0
-100...100
Working point for the correcting variable [%]
0
Ym.H
-100...100
Limitation of the mean value Ym [%]
5
L.Ym
0...9999
Max. deviation xw at the start of mean value calculation [phys. dimensions]
8
E.H2O
-1999...9999
Min. temperature for water cooling. Below set temperature no water
cooling happens
0
t.on
0,1...9999
Impulse lenght for water cooling. Fixed for all values of controller
output.The pause time is varied.
1
t.oFF
1...9999
Min. pause time for water cooling. The max. effective controller out-
put results from
t.on/(t.on+t.off)·100%
10
F.H2O
0,1...9999
Modification of the (non-linear) water cooling characteristic (see page 41)
1
oFFS
-120...120
Zero offset
0
q
PAr.2
(second parameterset
r
5.4)
Name
Value range Description
Default
Pb12
1...9999 1
Proportional band 1 (heating) in phys. dimensions (e.g. °C), 2. parameter set
100
Pb22
1...9999 1
Proportional band 2 (cooling) in phys. dimensions (e.g. °C), 2. parameter set
100
Ti22
0,1...9999
Integral action time 2 (cooling) [s], 2. parameter set
10
Ti12
0,1...9999
Integral action time 1 (heating) [s], 2. parameter set
10
Td12
0,1...9999
Derivative action time 1 (heating) [s], 2. parameter set
10
Td22
0,1...9999
Derivative action time 2 (cooling) [s], 2. parameter set
10
q
SEtP
Name
Value range Description
Default
SP.LO
-1999...9999
Set-point limit low for Weff
0
SP.Hi
-1999...9999
Set-point limit high for Weff
900
SP.2
-1999...9999
Set-point 2.
0
r.SP
0...9999
Set-point gradient [/min]
OFF
SP
-1999...9999
Set-point (only visible with BlueControl!)
0
SP.LO and SP.Hi should be within the limits of rnGH and rnGL see configura-
tion r Controller page