2 terminal connection 7, Inp2 current transformer 7, Out1/2 heating/cooling 7 – West Control Solutions KS 92-1 Programmer manual User Manual
Page 7: 2 terminal connection, Electrical connections, See chapter 11 "technical data, As input inp1, but without voltage, 2 out1/2 heating/cooling, 5 inp2 current tansformer, Power supply connection 1
2.2 Terminal connection
Power supply connection
1
See chapter 11 "Technical data"
Connection of outputs OUT1/2
2
Relay outputs (250V/2A),
potential-free changeover contact
Connection of outputs OUT3/4
3
a
relay (250V/2A), potential-free
changeover contact
universal output
b
current (0/4...20mA)
c
voltage (0/2...10V)
d
transmitter supply
e
logic (0..20mA / 0..12V)
Connection of input INP1
4
Input mostly used for variable x1 (pro-
cess value)
a
thermocouple
b
resistance thermometer (Pt100/ Pt1000/ KTY/ ...)
c
current (0/4...20mA)
d
voltage (0/2...10V)
Connection of input INP2
5
f
heating current input (0..50mA AC)
or input for ext. set-point (0/4...20mA)
g
potentiometer input for position
feedback
Connection of input INP3
6
As input INP1, but without voltage
Connection of inputs di1, di2
7
Digital input, configurable as switch or
push-button
Connection of inputs di2/3
8 (option)
Digital inputs (24VDC external), gal-
vanically isolated, configurable as
switch or push-button
Electrical connections
KS 90-1
p / KS 92-1
p
7
Terminal connection
6
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
17
(16)
L
N
+
5
4
3
2
1
8
7
15
2 OUT1/2 heating/cooling
L
N
+
_
SSR
3
4
5
6
9
10
11
12
13
14
15
1
2
3
4
5
8
9
10
11
12
13
14
15
17
(16)
2
1
8
7
6
7
Logik
5 INP2 current tansformer