beautypg.com

Configuration level – West Control Solutions KS 92-1 Programmer manual User Manual

Page 50

background image

4.4.7 Continuous controller with integrated positioner (

Cntr/ C.Fnc = 6 )

(

Cntr/ C.Fnc = 6 )

Basically, this controller function is a cascade. A slave controller with three-point
stepping behaviour working with position feedback Yp as process value (INP2 or
INP3) is added to a continuous controller.
ConF / Cntr

SP.Fn = 0

setpoint controller

C.Fnc = 6

continuous controller with
position controller

C.Act = 0

inverse output action
(e.g. heating applications)

ConF / InP.2: I.Fnc = 3

position feedback Yp

S.typ = 50

sensor e.g. potentiometer 0..160

W

ConF / Out.1: O.Act = 0

direct output action

Out.1

Y.1

=

1

control output Y1 active

Y.2

=

0

control output Y2 not active

ConF / Out.2: O.Act = 0

direct output action

Out.2

Y.1

=

0

control output Y1 not active

Y.2

=

1

control output Y2 active

PArA / Cntr: Pb1

= 0,1...9999

proportional band 1 (heating)
in units of the physical quantity
(e.g. °C)

ti1

= 1...9999

integral time 1 (heating) in sec.

td1

= 1...9999

derivative time 1 (heating) in sec.

t1

= 0,4...9999

min. cycle tim 1 (heating)

SH

= 0...9999

switching difference

Configuration level

Configuration examples

50

KS 90-1

p / KS 92-1

p

W

X

M

OUT.4

OUT.1

OUT.2

INP.2

Ypid

Position controller

INP.1

Y.1

Y.2

Master controller

Ycontinuous

X

W

SP

This manual is related to the following products: