Configuration level – West Control Solutions KS 92-1 Programmer manual User Manual
Page 50
4.4.7 Continuous controller with integrated positioner (
Cntr/ C.Fnc = 6 )
(
Cntr/ C.Fnc = 6 )
Basically, this controller function is a cascade. A slave controller with three-point
stepping behaviour working with position feedback Yp as process value (INP2 or
INP3) is added to a continuous controller.
ConF / Cntr
SP.Fn = 0
setpoint controller
C.Fnc = 6
continuous controller with
position controller
C.Act = 0
inverse output action
(e.g. heating applications)
ConF / InP.2: I.Fnc = 3
position feedback Yp
S.typ = 50
sensor e.g. potentiometer 0..160
W
ConF / Out.1: O.Act = 0
direct output action
Out.1
Y.1
=
1
control output Y1 active
Y.2
=
0
control output Y2 not active
ConF / Out.2: O.Act = 0
direct output action
Out.2
Y.1
=
0
control output Y1 not active
Y.2
=
1
control output Y2 active
PArA / Cntr: Pb1
= 0,1...9999
proportional band 1 (heating)
in units of the physical quantity
(e.g. °C)
ti1
= 1...9999
integral time 1 (heating) in sec.
td1
= 1...9999
derivative time 1 (heating) in sec.
t1
= 0,4...9999
min. cycle tim 1 (heating)
SH
= 0...9999
switching difference
Configuration level
Configuration examples
50
KS 90-1
p / KS 92-1
p
W
X
M
OUT.4
OUT.1
OUT.2
INP.2
Ypid
Position controller
INP.1
Y.1
Y.2
Master controller
Ycontinuous
X
W
SP