Page 24: Formulas

background image

3.7 Second PID parameter set

The process characteristic is frequently affected by various factors such as pro-
cess value, correcting variable and material differences.
To comply with these requirements, KS 90-1 can be switched over between two
parameter sets.
Parameter sets

PArA and PAr.2 are provided for heating and cooling.

Dependent of configuration (

ConF/LOG/Pid.2), switch-over to the second pa-

rameter set (

ConF/LOG/Pid.2) is via one of digital inputs di1, di2, di3,

key è or interface (OPTION).

g

Self-tuning is always done using the active parameter set, i.e. the second
parameter set must be active for optimizing.

Operation

Second PID parameter set

24

KS 90-1

p / KS 92-1

p

Parameter adjustment effects

Parameter

Control

Line-out of disturbances

Start-up behaviour

Pb1 higher increased damping

slower line-out

slower reduction of duty cycle

lower

reduced damping

faster line-out

faster reduction of duty cycle

td1 higher reduced damping

faster response to disturbances faster reduction of duty cycle

lower

increased damping

slower response to disturbances slower reduction of duty cycle

ti1 higher increased damping

slower line-out

slower reduction of duty cycle

lower

reduced damping

faster line-out

faster reduction of duty cycle

Formulas

K = Vmax * Tu

controller behavior

Pb1 [phy. units]

td1 [s]

ti1 [s]

With 2-point and
3-point controllers,
the cycle time must be
adjusted to
t1 / t2 £ 0,25 * Tu

PID

1,7 * K

2 * Tu

2 * Tu

PD

0,5 * K

Tu

OFF

PI

2,6 * K

OFF

6 * Tu

P

K

OFF

OFF

3-point-stepping

1,7 * K

Tu

2 * Tu