4.2 Set-point processing
The set-point processing structure is shown in the following picture:
Set-point gradient / ramp
To prevent setpoint step changes, a maximum rate of change is adjustable for pa-
rameter r setpoint r
r.SP. This gradient acts both in positive and negative di-
rection.
With parameter
r.SP set to OFFas in the factory setting, the gradient is switched
off and setpoint changes are made directly.