12.1 Reset to default

In the event of faulty configuration, the instrument can be reset to default.

In the event of faulty configuration, the instrument can be reset to default.

1 To start resetting, the operator must hold down the increment and the

decrement key ÈÌ simultaneously when switching on the supply voltage.

2 Subsequently, press the increment key È to select

YES.

3 Press Ù to confirm reset to default and to start copying (display COPY).
4 Subsequently, the instrument restarts.

In all other cases, no reset is necessary (cancellation via Timeout).

g

If one of the operating levels is disabled (using BlueControl

®

) and the Loc safety

switch is open, reset to default is not possible.

g

If a pass code was defined (using BlueControl

®

) and if the Loc safety switch is

open without an operating level being blocked, entry of the correct pass code is
prompted with text PASS after confirmation under 3. If the pass code is faulty,
resetting is not executed.

g

Copying

COPY may take several seconds.

g

An individual default data set can be generated using the BlueControl

®

Software.