Parameters 51, 3 input scaling, Input inp.1 – West Control Solutions KS 50-1 User Manual
Page 51: Input inp.2, Parameter setting level
5.3 Input scaling
When using current or voltage signals as input variables for
InP.1 or InP.2,
scaling of input and display values at parameter setting level is required. Specifi-
cation of the input value for lower and higher scaling point is in the relevant elec-
trical unit (mA/ V).
5.3.1
Input
Inp.1
g
Parameters
InL.1 , OuL.1, InH.1 and OuH.1 are only visible if
ConF / InP.1 / Corr = 3 is chosen.
In addition to these settings,
InL.1 and InH.1 can be adjusted in the range
(0...20mA / 0...10V) determined by selection of
S.tYP .
a
For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings of
InL.1 and OuL.1 as well as of InH.1
and
OuH.1 must correspond.
5.3.2
Input
InP.2
In addition to these settings,
InL.2 and InH.2 can be adjusted in the range
(0...20/ 50mA) determined by selection of
S.tYP.
Parameter setting level
Operating manual KS50-1
51
Input scaling
mA/V
phys.
quantity
mA / V
phys. quantity
OuH.x
OuL.x
InH.x
InL.x
S.tYP
Input signal
InL.1
OuL.1
InH.1
OuH.1
30
(0...20mA)
0 … 20 mA
0
-1999...9999
20
-1999...9999
4 … 20 mA
4
-1999...9999
20
-1999...9999
40
(0...10V)
0 … 10 V
0
-1999...9999
10
-1999...9999
2 … 10 V
2
-1999...9999
10
-1999...9999
S.tYP
Input signal
InL.2
OuL2
InH.2
OuH.2
30
0 … 20 mA
0
-1999...9999
20
-1999...9999
31
0 … 50 mA
0
-1999...9999
50
-1999...9999