Offset correction 54, Calibration level, Is possible off-line with process value simulator – West Control Solutions KS 50-1 User Manual

Page 54

background image

InH.1: The input value of the upper scaling point is displayed. .

The operator must adjust the upper input value by means of the
process value simulator and confirm the input value by pressing key Ù.

OuH.1: The display value of the upper scaling point is displayed.

Before calibration

OuH.1 is equal to InH.1.

The operator can correct the upper display value by pressing keys ÈÌ
Subsequently, he confirms the display value by pressing key Ù.

2-point correction

(

ConF/ InP.1 / Corr = 2 ):

is possible off-line with process value simulator

g

The parameters (

OuL.1,

OuH.1) altered at CAL level
can be reset by decreasing them
below the lowest adjustment
value (

OFF) using the

decrement key Ì .

Calibration level

54

KS50/52-1

X

standard setting

2-point correction

InL.1

InH.1

OuL.1

new

OuH.1

new

display

OuH.1

old

OuL.1

old