Technical data 65, Environmental conditions 65, Power supply 65 – West Control Solutions KS 50-1 User Manual
Page 65: Technical data
![background image](/manuals/370837/65/background.png)
Altitude
To 2000 m above sea level
Shock and vibration
Vibration test Fc (DIN 68-2-6)
Frequency:
10...150 Hz
Unit in operation:
1g or 0,075 mm
Unit not in operation:
2g or 0,15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock:
15g
Duration:
11ms
Electromagnetic compatibility
Complies with EN 61 326-1
(for continuous, non-attended operation)
GENERAL
Housing
Material:
Makrolon 9415 flame-retardant
Flammability class:
UL 94 VO, self-extinguishing
Plug-in module, inserted from the front
Safety test
Complies with EN 61010-1 (VDE 0411-1):
Overvoltage category II, Contamination class 2
Working voltage range 300 V, Protection class II
Certifications
Type tested to EN 14597 (replaces DIN
3440)
With certified sensors applicable for:
w
Heat generating plants with outflow
temperatures up to 120°C to DIN 4751
w
Hot-water plants with outflow temperatures
above 110°C to DIN 4752
w
Thermal transfer plants with organic transfer
media to DIN 4754
w
O
il-heated plants to DIN 4755
cULus-certification
(Type 1, indoor use)
File: E 208286
Mounting
Panel mounting with two fixing clamps at top/bottom
or right/left,
High-density mounting possible
Mounting position:
uncritical
Weight:
0,27kg
Accessories delivered with the unit
Operating manual (if selected in the order code)
Fixing clamps
operating hint (12 languages)
Technical data
KS50/52-1
65
Range
Input resistance
Accuracy
Resolution (
Ô)
0-10 Volt
~ 110 kΩ
Я 0,1 %
Я 0,6 mV
0-20 mA
49
Ω (voltage requirement ß 2,5 V)
Я 0,1 %
Я 1,5 μA
Table 3 Current and voltage measuring ranges
Type
Sens. current
Range
Accuracy
Resolution (
Ô)
Pt100
0,2mA
-200...100°C
-140...212°F
ß 1K
0,1K
Pt100
-200...850°C
-140...1562°F
ß 1K
0,1K
Pt1000
-200...850°C
-140...392°F
ß 2K
0,1K
KTY 11-6
-50...150°C
-58...302°F
ß 2K
0,05K
Table 2 Resistance transducer measuring ranges
Thermocouple type
Range
Accuracy
Resolution (
Ô)
L
Fe-CuNi (DIN)
-100...900°C
-148...1652°F
ß 2K
0,1 K
J
Fe-CuNi
-100...1200°C
-148...2192°F
ß 2K
0,1 K
K
NiCr-Ni
-100...1350°C
-148...2462°F
ß 2K
0,2 K
N
Nicrosil/Nisil
-100...1300°C
-148...2372°F
ß 2K
0,2 K
S
PtRh-Pt 10%
0...1760°C
32...3200°F
ß 2K
0,2 K
Table 1 Thermocouple measuring ranges