Error status 15, Operation – West Control Solutions KS 50-1 User Manual

Page 15

background image

Name

Description

Cause

Possible remedial action

LooP

Control loop alarm

(LOOP)

  Input signal defective or not

connected correctly

  Output not connected correctly

  Check heating or cooling circuit

  Check sensor and replace it, if

necessary

  Check controller and switching

device

AdA.H

Self-tuning heating

alarm
(ADAH)

  See Self-tuning heating error

status

  see Self-tuning heating error

status

AdA.C

Self-tuning heating

alarm cooling
(ADAC)

  See Self-tuning cooling error

status

  see Self-tuning cooling error

status

LiM.1

stored limit alarm 1

  adjusted limit value 1 exceeded   check process

Lim.2

stored limit alarm 2

  adjusted limit value 2 exceeded   check process

Lim.3

stored limit alarm 3

  adjusted limit value 3 exceeded   check process

Inf.1

time limit value

message

  adjusted number of operating

hours reached

  application-specific

Inf.2

duty cycle message
(digital ouputs)

  adjusted number of duty cycles

reached

  application-specific

g

Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3, the è-key or the Ò-key or the.
Configuration, see page 36:

ConF / LOGI / Err.r

g

If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Not applicable to heating current alarm.

Error status:
Self-tuning heating (

ADA.H) and cooling ( ADA.C) error status:

Error status

Description

Behaviour

0

No error

3

Faulty control action

Re-configure controller (inverse i direct)

4

No response of process

variable

The control loop is perhaps not closed: check sensor,

connections and process

5

Low reversal point

Increase (

ADA.H) max. output limiting Y.Hi or

decrease (

ADA.C) min. output limiting Y.Lo

6

Danger of exceeded set-point

(parameter determined)

If necessary, increase (inverse) or reduce (direct)

set-point

7

Output step change too small

(

{

y > 5%)

Increase (

ADA.H) max. output limiting Y.Hi or

reduce (

ADA.C) min. output limiting Y.Lo

8

Set-point reserve too small

Increase set-point (invers), reduce set-point (direct)
or increase set-point range
(r

PArA / SEtp / SP.LO and SP.Hi )

9

Impulse tuning failed

The control loop is perhaps not closed: check sensor,

connections and process

Operation

KS50/52-1

15

Maintenance manager / Error list