6 calibration level 53, Calibration level (cal) 53 - 55, Calibration level – West Control Solutions KS 50-1 User Manual

Page 53: Offset correction

background image

Offset correction

(

ConF/ InP.1 / Corr =1 ):

possible on-line at the process

2-point correction (

ConF/ InP.1 / Corr = 2):

InL.1: The input value of the lower scaling point is displayed.

The operator must adjust the lower input value by means of a
process value simulator and confirm the input value by pressing key Ù.

OuL.1: The display value of the lower scaling point is displayed.

Before calibration,

OuL.1 is equal to InL.1.

The operator can correct the lower display value by pressing the ÈÌ
keys. Subsequently, he confirms the display value by pressing key Ù.

Calibration level

KS50/52-1

53