3.6 Manual tuning
The optimization aid should be used with units on which the control parameters
shall be set without self-tuning.
For this, the response of process variable x after a step change of correcting va-
riable y can be used. Frequently, plotting the complete response curve (0 to
100%) is not possible, because the process must be kept within defined limits.
Values T
g
and x
max
(step change from 0 to 100 %) or
Dt and Dx (partial step re-
sponse) can be used to determine the maximum rate of increase v
max
.
y
=
correcting variable
Y
h
=
control range
Tu
=
delay time (s)
Tg
=
recovery time (s)
X
max
=
maximum process value
V
max
=
Xmax
Tg
=
{
{
x
t
= max. rate of increase of process value
The control parameters can be determined from the values calculated for delay time T
u
,
maximum rate of increase v
max
, control range X
h
and characteristic K according to the
formulas given below. Increase Xp, if line-out to the set-point oscillates.