Configuration 30, Inp.1, Configuration level – West Control Solutions KS 50-1 User Manual
Page 30
Name
Value range Description
Default
CYCL
Characteristic for 2-point- and 3-point-controllers
0
0
standard
1
water cooling linear
2
water cooling non-linear
3
with constant cycle
tunE
Auto-tuning at start-up
0
0
At start-up with step function
1
At start-up with impulse function. Setting for fast controlled systems
(e.g. hot runner control)
2
Always step attempt during start-up
Strt
Start of auto-tuning
0
0
no automatic start (manual start via front interface)
1
Manual or automatic start of auto-tuning at power on or when
oscillating is detected
Adt0
Optimization of T1, T2 (only visible with BlueControl!)
0
0
Automatic optimization
1
No optimization
InP.1
Name
Value range Description
Default
S.tYP
Sensor type selection
1
0
thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
thermocouple type J (-100...1200°C) , Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
20
Pt100 (-200.0 ... 100,0 °C)
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 850.0 °C)
23
special 0...4500 Ohm (pre-defined as KTY11-6)
30
0...20mA / 4...20mA
Scaling is required. (see chp.5.3 page 51)
40
0...10V / 2...10V
Scaling is required. (see chp. 5.3 page 51)
S.Lin
Linearization (only at
S.tYP
= 23 (KTY 11-6),
30
(0..20mA) and 40 (0..10V) adjustable)
0
0
none
1
Linearization to specification. Creation of linearization table with
BlueControl (engineering tool) possible. The characteristic for
KTY 11-6 temperature sensors is preset.
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL level)
2
2-point correction (at
CAL level)
3
Scaling (at
PArA level)
Configuration level
Configurations
30
KS50/52-1