Name

Value range Description

Default

CYCL

Characteristic for 2-point- and 3-point-controllers

0

0

standard

1

water cooling linear

2

water cooling non-linear

3

with constant cycle

tunE

Auto-tuning at start-up

0

0

At start-up with step function

1

At start-up with impulse function. Setting for fast controlled systems

(e.g. hot runner control)

2

Always step attempt during start-up

Strt

Start of auto-tuning

0

0

no automatic start (manual start via front interface)

1

Manual or automatic start of auto-tuning at power on or when

oscillating is detected

Adt0

Optimization of T1, T2 (only visible with BlueControl!)

0

0

Automatic optimization

1

No optimization

InP.1

Name

Value range Description

Default

S.tYP

Sensor type selection

1

0

thermocouple type L (-100...900°C) , Fe-CuNi DIN

1

thermocouple type J (-100...1200°C) , Fe-CuNi

2

thermocouple type K (-100...1350°C), NiCr-Ni

3

thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

thermocouple type S (0...1760°C), PtRh-Pt10%

5

thermocouple type R (0...1760°C), PtRh-Pt13%

20

Pt100 (-200.0 ... 100,0 °C)

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0 ... 850.0 °C)

23

special 0...4500 Ohm (pre-defined as KTY11-6)

30

0...20mA / 4...20mA
Scaling is required. (see chp.5.3 page 51)

40

0...10V / 2...10V
Scaling is required. (see chp. 5.3 page 51)

S.Lin

Linearization (only at

S.tYP

= 23 (KTY 11-6),

30

(0..20mA) and 40 (0..10V) adjustable)

0

0

none

1

Linearization to specification. Creation of linearization table with

BlueControl (engineering tool) possible. The characteristic for

KTY 11-6 temperature sensors is preset.

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction (at

CAL level)

2

2-point correction (at

CAL level)

3

Scaling (at

PArA level)

Configuration level

Configurations

30