Page 42
4.5.2
2-point and continuous controller (inverse)
ConF
/
Cntr
SP.Fn
= 0
set-point / cascade controller
C.Fnc
= 1
2-point and continuous controller (PID)
C.Act
= 0
inverse action
(e.g. heating applications)
ConF / Out.1:
O.Act
= 0
action
Out.1 direct
Y.1
= 1
control output Y1 active
ConF / Out.3:
O.tYP
= 1 / 2
Out.3 Type ( 0/4 … 20mA)
Out.0
= -1999...9999
scaling analog output 0/4mA
Out.1
= -1999...9999
scaling analog output 20mA
O.Src
= 1
controller output y1 (continuous)
PArA / Cntr:
Pb1
= 1...9999
proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1
= 0,1...9999
integral time 1 (heating) in sec.
td1
= 0,1...9999
derivative time 1 (heating) in sec.
t1
= 0,4...9999
min. cycle time 1 (heating)
PArA / SEtP:
SP.LO
= -1999...999
set-point limit low for Weff
SP.Hi
= -1999...9999
set-point limit high for Weff
g
For direct action, the controller action must be changed
(
ConF / Cntr / C.Act = 1 ).
Configuration level
Configuration examples
42
KS50/52-1
InH.1
InL.1
SP.LO
SP
SP.Hi
Out.1Â
InP.1Ê
100%
0%
PB1
Out.3Â
20 mA
0/4 mA
PB1
setpoint
Relay-
output
process value