beautypg.com

2 2-point and continuous controller (inverse) 42, Point controller 42 - 43, Point and continuous controller (inverse) – West Control Solutions KS 50-1 User Manual

Page 42

background image

4.5.2

2-point and continuous controller (inverse)

ConF

/

Cntr

SP.Fn

= 0

set-point / cascade controller

C.Fnc

= 1

2-point and continuous controller (PID)

C.Act

= 0

inverse action
(e.g. heating applications)

ConF / Out.1:

O.Act

= 0

action

Out.1 direct

Y.1

= 1

control output Y1 active

ConF / Out.3:

O.tYP

= 1 / 2

Out.3 Type ( 0/4 … 20mA)

Out.0

= -1999...9999

scaling analog output 0/4mA

Out.1

= -1999...9999

scaling analog output 20mA

O.Src

= 1

controller output y1 (continuous)

PArA / Cntr:

Pb1

= 1...9999

proportional band 1 (heating)
in units of phys. quantity (e.g. °C)

ti1

= 0,1...9999

integral time 1 (heating) in sec.

td1

= 0,1...9999

derivative time 1 (heating) in sec.

t1

= 0,4...9999

min. cycle time 1 (heating)

PArA / SEtP:

SP.LO

= -1999...999

set-point limit low for Weff

SP.Hi

= -1999...9999

set-point limit high for Weff

g

For direct action, the controller action must be changed
(

ConF / Cntr / C.Act = 1 ).

Configuration level

Configuration examples

42

KS50/52-1

InH.1

InL.1

SP.LO

SP

SP.Hi

Out.1Â

InP.1Ê

100%

0%

PB1

Out.3Â

20 mA

0/4 mA

PB1

setpoint

Relay-
output

process value