Special functions

8.1 Start-up circuit

The start-up circuit is a special function for temperature control, e.g. hot runner
control. High-performance heating cartridges with magnesium oxyde insulation
material must be heated slowly to remove moisture and prevent destruction.

Operating principle:

1 After switching on the supply voltage, line-out to the start-up set-point SP.St

is using a maximum start-up correcting value of

Y.St.

2 The start-up holding time t.St is started one K below the start-up set-point

(

SP.St-1K).

3 Subsequenlyt, the process is lined out to set-point W.

4 If the process value drops by more than 40 K below the start-up set-point

(

SP.St-40K) due to a disturbance, the start-up procedure is re-started ( 5, 6, 7 ).

g

With W <

SP.St, W is used as set-point. The start-up holding time t.St is omitted.

g

If the gradient function (

PArA/ SEtP/ r.SP ¹ OFF) was selected, start-up value

SP.St is reached with the adjusted gradient r.SP.

g

With the boost function (see chapter 8.2) selected, W is increased by SP.bo
during time

t.bo .

The following settings can be selected:

SP.Fn = 10 set-point + start-up circuit

The start-up circuit is effective only with the internal set-point.

SP.Fn = 11set-point, SP.E /SP.2 + start-up circuit

The start-up circuit is effective also with the external set-point SP.E and the 2nd
set-point SP.2.

Special functions

Start-up circuit

56