beautypg.com

3 input scaling 52, 1 input inp.1 52, 2 input inp.2 52 – West Control Solutions KS 50-1 User Manual

Page 52: Input scaling 52, Мщ м

background image

6

Calibration level

g

Measured value correction (

CAL)

is visible only if

ConF / InP.1 / Corr = 1 or 2 is selected.

w

To access the calibration level, press the key Ù for 3 seconds and then the
key Ì to select the

CAL-Menu item. Press Ù to confirm.

w

If the password function is activated, a prompt for the

PASS is displayed.

In the calibration menu (

CAL), the measured value can be adapted. Two me-

thods are available :

Offset correction (

ConF/ InP.1 / Corr =1 ):

InL.1: The input value of the scaling point is displayed.

The operator must wait, until the process is at rest.
Subsequently, the operator acknowledges the input value by pressing
key Ù.

OuL.1: The display value of the scaling point is displayed.

Before calibration,

OuL.1 is equal to InL.1. The operator can correct

the display value by pressing keys ÈÌ .
Subsequently, he confirms the display value by pressing key Ù.

Calibration level

52

KS50/52-1

ConF

126

125

126

PArA

126

3 Sek

PASS

Щ

(

)

М

Щ

М

CAl

126

r

М

Щ

3 sec.

r

PArA

CAL

r Ù r

InP.1

Ù

r

InL.1

r

r Ù

r

:

OuL.1

r

r Ù

End

r

r Щ

М

И

125

126

SP.X

run

Err

Ada