beautypg.com

Configuration 31, Inp.2, Configuration level – West Control Solutions KS 50-1 User Manual

Page 31

background image

Name

Value range Description

Default

fAI1

Forcing INP1 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

InP.2

Name

Value range Description

Default

I.Fnc

Function selection of INP2

1

0

no function (subsequent input data are skipped)

1

heating current input

2

external set-point (

SP.E)

5

default correcting variable Y.E (switchover ->

LOGI/ Y.E)

S.tYP

Sensor type selection

31

30

0...20mA / 4...20mA
Scaling is required. (see chp. 5.3 page 51)

31

0...50mA AC
Scaling is required. (see chp.5.3 page51)

fAI2

Forcing INP2 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

Lim

Name

Value range Description

Default

Fnc.1
Fnc.2
Fnc.3

Function of limit 1/2/3

1

0

switched off

1

measured value monitoring

2

Measured value monitoring + alarm status storage. A stored

limit value can be reset via error list,

è

-key, Ò-key or a

digital input ( ->

LOGI/ Err.r)

Src.1
Src.2
Src.3

Source of Limit 1/2/3

1

0

process value

1

control deviation xw (process value - set-point)

2

control deviation xw (with suppression after start-up and

set-point change)

6

effective setpoint Weff

7

correcting variable y (controller output)

8

control variable deviation xw (actual value - internal

setpoint) = deviation alarm to internal setpoint

11

Control deviation Xw (=relative alarm) with suppression

after start-up or set-point change without time limit.

HC.AL

Alarm heat current function (INP2)

0

0

switched off

1

Overload short circuit monitoring

2

Break and short circuit monitoring

LP.AL

Monitoring of control loop interruption for heating

0

0

switched off / inactive

1

active
If

ti1=0 LOOP alarm is inactive!

Configuration level

KS50/52-1

31

Configurations