w

Press the Ù - key to change to the next parameter.

w

After the last parameter of a group,

donE is displayed and followed by auto-

matic changing to the next group

g

Return to the beginning of a group, by pressing the Ù key for 3 sec.

g

Unless a key is pressed during 30 seconds, the controller returns to the process
value and setpoint display ( Time Out = 30 sec. )

g

Resetting the configuration parameters to default

r chapter 12.1 (page 68)

5.2 Parameters

Cntr

Name

Value range

Description

Default

Pb1

1...9999 1

Proportional band 1 (heating) in phys. dimensions (e.g. °C)

100

Pb2

1...9999 1

Proportional band 2 (cooling) in phys. dimensions (e.g. °C)

100

ti1

1...9999

Integral action time 1 (heating) [s]

180

ti2

1...9999

Integral action time 2 (cooling) [s]

180

td1

1...9999

Derivative action time 1 (heating) [s]

180

td2

1...9999

Derivative action time 2 (cooling) [s]

180

t1

0,4...9999

Minimal cycle time 1 (heating) [s]. The minimum impulse is 1/4 x t1

10

t2

0,4...9999

Minimal cycle time 2 (cooling) [s]. The minimum impulse is 1/4 x t2

10

SH

0...9999

Neutral zone or switching differential for on-off control

[phys. dimensions)

2

d.SP

-1999...9999

Trigger point seperation for additional contact

D / Y / Off [

phys. dimensions]

100

tP

0,1...9999

Minimum impulse [s]

OFF

tt

3...9999

Motor travel time [s]

60

Y2

-120...120

2. correcting variable

0

Y.Lo

-120...120

Lower output limit [%]

0

Y.Hi

-120...120

Upper output limit [%]

100

Y.0

-120...120

Working point for the correcting variable [%]

0

Ym.H

-120...120

Limitation of the mean value Ym [%]

5

L.Ym

0...9999

Max. deviation xw at the start of mean value calculation

[phys. dimensions]

8

E.H2O

-1999...9999

Min. temperature for water cooling. Below the set temperature

no water cooling happens.

120

t.on

0,1...9999

Impulse lenght for water cooling. Fixed for all values of

controller output.The pause time is varied.

0,1

t.oFF

1...9999

Min. pause time for water cooling. The max. effective controller

output results from

t.on/(t.on+t.off)·100%

2

F.H2O

0,1...9999

Modification of the (non-linear) water cooling characteristic

(see page 39)

0,5

1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /

0,001 is possible.

Parameter setting level

Parameters

48