Othr, Configuration level – West Control Solutions KS 50-1 User Manual

Page 36

background image

othr

Name

Value range

Description

Default

bAud

Baudrate of the interface (only visible with OPTION)

2

0

2400 Baud

1

4800 Baud

2

9600 Baud

3

19200 Baud

Addr

1...247

Address on the interace (only visible with OPTION)

1

PrtY

Data parity on the interface (only visible with OPTION)

1

0

no parity (2 stop bits)

1

even parity

2

odd parity

dELY

0...200

Delay of response signal [ms] (only visible with OPTION)

0

Unit

Unit

1

0

without unit

1

°C

2

°F

dP

Decimal point (max. number of digits behind the decimal point)

0

0

no digit behind the decimal point

1

1 digit behind the decimal point

2

2 digits behind the decimal point

3

3 digits behind the decimal point

LED

Function allocation of the status LEDs1 / 2 / 3

0

0

OUT1, OUT2, OUT3

1

Heating, Alarm 2, Alarm 3

2

Heating, Cooling, Alarm 3

C.dEl

0..200

Modem delay [ms]

0

FrEq

Switching 50 Hz / 60 Hz (only visible with BlueControl!)

0

0

50 Hz

1

60 Hz

MASt

Modbus Master / Slave (only visible with BlueControl

®

!)

0

0

No

1

Yes

Cycl

0 ... 240

Mastercycle (sec.) (only visible with BlueControl

®

!)

120

Adr0

-32768 ... 32767 Destination address (only visible with BlueControl

®

!)

1100

AdrU

-32768 ... 32767 Source address (only visible with BlueControl

®

!)

1100

Numb

0 ... 100

Number of data (only visible with BlueControl

®

!)

1

ICof

Block controller off (only visible with BlueControl!)

0

0

Released

1

Blocked

Configuration level

Configurations

36

KS50/52-1