3.4 Maintenance manager / Error list

With one or several errors, the extended operating level al-
ways starts with the error list. Signalling an actual entry in
the error list (alarm, error) is done by the Err LED in the
display. This is applicable only, if at least one limit value
function, the loop alarm or the heating current alarm is ac-
tivated. For display of the error list, press Ù twice.

Err LED status

Signification

Proceed as follows

blinks
(Status

2)

Alarm due to existing

error

Determine the error type in the error list after

removing the error the device changes to Status

1

lit
(Status

1)

Error removed,
Alarm not acknowledged

Acknowledge the alarm in the error list pressing key

È or Ì the alarm entry is deleted (Status 0).

off
(Status

0)

No error,
all alarm entries deleted

not visible, exept when ackowledging

Error list:

Name

Description

Cause

Possible remedial action

E.1

Internal error,
cannot be removed

  E.g. defective EEPROM

  Contact PMA service

  Return unit to our factory

E.2

Internal error, can be

reset

  e.g. EMC trouble

  Keep measurement and power

supply cables in separate runs

  Ensure that interference

suppression of contactors is
provided

E.4

Hardware error

  Codenumber and hardware are

not identical

  Contact PMA service

  Electronic-/Optioncard must be

exchanged

FbF.1

Sensor break INP1

  Sensor defective

  Faulty cabling

  Replace INP1 sensor

  Check INP1 connection

Sht.1

Short circuit INP1

  Sensor defective

  Faulty cabling

  Replace INP1 sensor

  Check INP1 connection

POL.1

INP1polarity error

  Faulty cabling

  Reverse INP1 polarity

FbF.2

Sensor break INP2

  Sensor defective

  Faulty cabling

  Replace INP2 sensor

  Check INP2 connection

Sht.2

Short circuit INP2

  Sensor defective

  Faulty cabling

  Replace sensor INP2

  Check INP2 connection

POL.2

INP2 polarity

  Faulty cabling

  Reverse INP2 polarity

HCA

Heating current

alarm (HCA)

  Heating current circuit

interrupted, I<

HC.A or I>

HC.A (dependent of
configuration)

  Heater band defective

  Check heating current circuit

  If necessary, replace heater band

SSr

Heating current short

circuit (SSR)

  Current flow in heating circuit

at controller off

  SSR defective

  Check heating current circuit

  If necessary, replace solid-state

relay