U = 6...30 V; I

Low

< 110 mA; U

Low

< 2 V;

I

High

< 900 µA (@ U=30V) or I

High

= 200 µA (@ U=8V)

Data: Ex-i switching output

Maximum safety values:
U

i

= 30V; I

i

= 250mA; P

i

= 1W; C

i

5nF; L

i

0

Type active (current source)
Current range 4-20 mA (error: 2mA or 22mA)
Accuracy/linearity 0.3 % (rel. 20 mA; 20°C, R

B

=100

)

Temperature drift < 200 ppm/K (typical 70 ppm/K)
Load < 250 Ohm
Load influence < 0.1 % (rel. 20 mA; R

B

= 0...250

Power supply influence < 0.1 % (rel. 20 mA; U

B

in Tol. limits)

Used as switching output:
Low status current < 2 mA
High status current = 22 mA (Load < 500

Data: current output (non-
communicable; in combination
with RS485)

Open loop voltage < 18 V
Baudrate: 1200 to 38400 Baud
Address: 0 to 255

Data: RS485 interface

Protocols: Krohne protocol,Modbus-RTU, HART

®

Data: PROFIBUS-PA

9... 30 V; Base current 10.5 mA; Fault current 6 mA

Maximum safety values:
U

i

= 30V; I

i

= 300mA; P

i

= 4.2W; C

i

5nF; L

i

0

Suitable for connection to intrinsically safe Fieldbus systems
acc. PTB’s FISCO model

Data: FF interface

as for PROFIBUS-PA
Local display
Current output: error signal 2 mA (Ex-i: 3.6 mA) or 22 mA
Switching output: open or close contact

Signal on alarm

Digital interfaces: error flags
(only with Ex-e current output HART

®

):

temporarily "freezing" of measurement

Digital input

Voltage: 5...28 V DC; Input resistance: > 1 k

Measuring accuracy

Temperature: +20°C
Pressure: 1013 mbar abs.
Air humidity: 65%
Well reflecting product (e.g. water) with calm surface
Vessel diameter > 5 m
Mounting distance from wall min. 1/5 × tank height

Reference conditions

No interference reflections within the beam angle (± 6°)
(dependent on measuring distance a)
Under reference conditions:
a: block dist. ... 1m: ± 3...2 cm
a: 1 m ... 20 m: ± 2 mm

Error of measurement

a: 20 m ... 35 m: ± 0.01 % of distance

Repeatability

< 0.5 × Error of measurement

Measured-value resolution

0.1 mm

Hysteresis

< 0.05 × Error of measurement

Transient recovery time

Dependent on programmed time constant (1 ... 100 s)

Turn-on drift / characteristics

First measured value: approx. 1 minute after switching on
full measuring accuracy: after 2 minutes operating time

Long-term drift

Within specified error of measurement