Page 10: Communication

background image

10

BM 70 M

HART
Master

4...20 mA

4.3

Ex-i current output HART

®

(type of protection: Ex de [ia])

Function

Level, distance, volume (conversion table) or reflection; and error
identification; passive output (current sink)

Current

4-20 mA; without or with error message (3.6 mA / 22 mA);
4 mA constant, adjustable for HART

®

-Multidrop

Temperature drift

< 100 ppm/K (typically 30 ppm/K)

Accuracy/linearity

0.05 % (rel. 20 mA; at T = 20°C, 10 V supply voltage and nominal
operating voltage)

Supply voltage U

8-30 V (between terminals 31 and 32)

Load impedance

< (US - 8V) / 22 mA. (US = external supply voltage)

Effect of supply voltage

< 0.02 % (rel. 20 mA for U = 8...30 V)

Effect of power

< 0.02 % (rel. 20 mA for UB within limits of tolerance)

Note

Digital input not available

Optional switching output (terminals 41/42):

Can be programmed as limit switch, alarm contact or error message. The contact is open in the
deenergized condition.

Operating data

6...30 V; I

Low

< 110 mA; U

Low

< 2V; I

High

< 900 µA (U=30V) and I

High

= 200 µA (U=8V)

Ex-i safety limits

Signal circuit in type of protection: Intrinsic Safety EEx ia IIC/IIB or EEx ib IIC/IIB for connection to
a certified intrinsically safe circuit with the following peak values:
U

o

= 30 V; I

k

= 250 mA

Effective inner capacitance

0; effective inner inductance

0

4.4 HART

®

communication

The HART

®

Communications protocol can, in accordance with the Rosemount Standard, be used

with a BM 70 M.
Electrical connection: see Section 7.6.

There are two ways of using the HART

®

Communication:

Point-to-point connection

Multipoint connection (Multidrop)

between the BM 70 M and the HART

®

master equipment.
A BM 70 M can be used either with an
Ex-e current output HART

®

or with an

Ex-i current output HART

®

.

with up to 15 devices (BM 70 M or other HART

®

equipment), in parallel on a 2-wire bus. A BM 70 M is
normally used with Ex-i current output, but an Ex-e
current output can also be used (constant 4 mA in
both cases).

HART
Master

4mA

4mA

4mA

4mA

other

HART
device

HART
device

other