8.6.3 Block distance, antenna type and antenna extension

Fct. 3.1.2 BLOCKDIST

Caked deposits or contamination of the antenna, for example, can cause faulty measurements
directly below the antenna. The function "block distance" is used to specify a zone below the
flange in which measurements are not to be carried out.

Signals within the block distance are suppressed; a rise in the level above this limit will result
in a measurement corresponding to a distance = block distance, when Fct. 3.5.6 BD-DETECT
= ON.

Unit and setting range: same as Fct. 3.1.1 TANKHEIGHT.

Recommended minimum value (see also Sect. 3.3):
- for stilling wells
- antenna length + 300 mm
- all other versions in storage tanks:
- antenna extension + antenna length + 100 mm
- all other versions in process tanks:
- antenna extension + antenna length + 200 mm

Fct. 3.1.3 ANTENNA

The antenna type is factory-set here.

STANDARD

BM 70 M: only STANDARD setting possible.

Fct. 3.1.4 ANT.EXTENS.

The length of the supplied antenna extension is factory-set here.

Unit and setting range: same as Fct. 3.1.1 TANKHEIGHT.

This setting may only be changed when a longer or shorter antenna extension is installed.
Otherwise faulty measurements may result because the BM 70 M allows for this length when
measuring. After changing any antenna extension, record a new empty spectrum, see Sect.
8.6.12. When a curved antenna extension is used, only the vertical component (vertical offset)
should be entered here.
Example (S-shaped extension): Fct. 3.1.4 = 323 mm.

8.6.4 Distance

piece

Fct. 3.1.5 DIST.PIECE

The length of any supplied distance piece above the mounting flange is factory-set here.

Setting range: 0 ... 2000 mm

Default value: 0 mm

The value of 120 mm should be entered for the high-temperature version of the flange system.
When a curved antenna extension is used, the horizontal component of this extension should
additionally be entered (= geometric length of the pipe minus the vertical offset).
Example (see drawing above): Fct. 3.1.5 = 300 mm.

323 mm

300 mm

(Fct. 3.1.4)

(Fct. 3.1.5)