BM 70 M
Function (Fct.)
Enter range
Default value
Description
Options OFF
ON
3.5.2
EMPTY.SPEC.
RECORD
OFF *
Switch the empty-
tank spectrum (profile
of the empty tank)
on/off, or make new
recording.
3.5.3
TIMECONST.
Value
10... 100 [s]
30 s
Input of the time
constant for
measured-value
filtering (low-pass).
3.5.4
TRACING.VEL. Value
0.01 ... 1.00 [m/Min]
0.10 m/min
Input of the maximum
rate of change in the
level that can occur
in operation.
Options NO
3.5.5
MULT.REFL.
YES
NO
Switch the multi-
reflection identifier
on/off.
Options NO
3.5.6
BD-DETECT
YES
YES
Switch the block
distance (overfill)
detector on/off.
Options OFF
3.5.7 FUNCT. FTB
PARTIAL
OFF
Select function of the
tank bottom tracking
system.
3.5.8 EPSILON R
Enter
1.1000 ... 8.0000
2.0000
Input of the relative
permittivity of the
product for the tank
bottom tracking
system.
Options STORAGE
TANK
3.5.9
TANKTYPE
PROC.TANK.
PROC.TANK.
Select the tank type.
3.6 SW.OUTP.S
Options OFF
LEVEL
DISTANCE
CONVERSION
REFLECTION
ERROR
OPEN
3.6.1 FUNCTION S
ERROR
CLOSED
ERROR
OPEN
Select the function of
the switching output.
Option HIGH
3.6.2 TYPE S
LOW
HIGH
Select type of limit
value for the
switching output.
(not applicable to
Function OFF,
ERROR OPEN or
ERROR CLOSED)