beautypg.com

KROHNE BM 70 M User Manual

Page 41

background image

BM 70 M

41

Function I (Fct 3.3.1)

CONVERSION

Range I (Fct. 3.3.2)

4 - 20 mA

Scaling 4 mA (Fct. 3.3.3)

0.00 m

3

, corresponds to 4 mA

Current output I

Scaling 20 mA (Fct. 3.3.4)

16.80 m

3

, corresponds to

20 mA

Function S (Fct. 3.6.1)

LEVEL

Type S (Fct. 3.6.2)

LOW (=if level drops below
threshold)

Threshold(Fct. 3.6.3)

5.00 m

Switching output

Hysteresis (Fct. 3.6.4)

0.10 m

Function, display (Fct. 3.2.1)

CONVERSION

Display

Unit, conversion (Fct. 3.2.2)

m

3

(cubic meter)

8.6

Description of functions

8.6.1 Choice of units

Level/distance units

Select under Fct. 3.1.1 TANKHEIGHT

m

cm

mm

inch

Ft

The unit selected here is also valid for the following functions:
Block distance

Fct. 3.1.2

Antenna extension

Fct. 3.1.4

Scaling 4 mA value, current output

Fct. 3.3.3

Scaling 20 mA value, current output

Fct. 3.3.4

Range for partial tank bottom tracing

Fct. 3.5.2

Threshold (limit value), switching output

Fct. 3.6.3

Hysteresis, switching output

Fct. 3.6.4

Tracking speed,

Fct. 3.5.4
(in m/min when Fct.3.1.1 = m, cm or mm
or in ft/min when Fct.3.1.1 = inch or ft)

The Fct. 3.2.2 (length unit for display) can be set independently of the unit selected under Fct.
3.1.1.

Conversion units

By conversion is meant the transposition of an arbitrary level value into a "conversion value"
(usually volume), so as, for example, to realise a non-linear function as a factor of the level.
Options under Fct. 3.2.3 UNIT.CONV.

l ( = litres)

US Gal

GB Gal (Gal = gallons)

Ft3

bbl (petroleum barrels)