BM 70 M

Function (Fct.)

Enter range

Default
value

Description

3.1.8 TB. OFFSET

Enter
-100.00 ... + 100.00 [m]

0.00 m

To input the tank
bottom offset
(relocation of the lower
reference point).

3.2 DISPLAY

Options LEVEL
DISTANCE
CONVERSION

3.2.1

FCT.DISP.

REFLECTION

LEVEL

Select function of the
display (value to be
displayed).

Options m
cm
mm
inch
Ft
PERCENT

3.2.2

UNIT.LENGTH

BARGRAPH

Meter [m]

Select unit for length
value to be displayed
(level/distance).
The unit selected here
is used only for display
of length values.

Options m3
l
US

Gal

GB

Gal

Ft3
bbl
PERCENT
BARGRAPH

3.2.3

UNIT.CONV

USER

UNIT

Cubic
meter
[m3]

Select unit for
conversion values to
be displayed ("volume
table").
The unit selected here
is used only for display
of the conversion
value

3.2.4 USER UNIT

Text entry
10 ASCII characters

________

Input of freely
programmable unit for
the conversion table
(max. 10 characters).

Options NO

3.2.5 ERROR MSG.

YES

YES

Select whether error
messages are to be
shown in the display

3.3 SIGNAL.OUTP.

Options OFF
LEVEL
DISTANCE
CONVERSION
REFLECTION

3.3.1 FUNCTION I

SW.OUTP.

LEVEL

Select function of the
current output
(measured value to be
displayed, or
OFF = current output
switched off = constant
4 mA).

Options 4-20

mA/E22

4-20

mA/E2

3.3.2 RANGE I

4-20

mA

4-20 mA/
E22

Select the range for
the current output and
error output.

3.3.3 SCALE 4 mA

Enter
-200.00 ... +200.00 [m]
0.00... 99999.99 [m3]
0 ... 100 [Refl.]

0.00 m
0.00 m3
0

Input the lower range
value for output to the
current output.
(Input is dependent on
the selected function
of the current output.
The values for level
and distance include
the tank bottom and
refe rence offset,
resp.).