beautypg.com

KROHNE BM 70 M User Manual

Page 34

background image

34

BM 70 M

8.4

Table of settable functions (Versions 4.04 – 4.06)

Function (Fct.)

Enter range

Default
value

Description

1.0 OPERATION
1.1 DISPLAY

LEVEL
DISTANCE
CONVERSION

1.1.1

FCT.DISP

Options

REFLECTION

LEVEL

Select function of
display
(value to be displayed).

m
cm
mm
inch
Ft
PERCENT

1.1.2

UNIT.LENGTH Options

BARGRAPH

Meter [m]

Select unit for value of
length to be displayed
(level/distance).

m3
l
US Gal
GB Gal
Ft3
bbl
PERCENT
BARGRAPH

1.1.3 UNIT. CONV

Options

USER UNIT

Cubic meter
[m3]

Select unit for
conversion value to be
displayed ("volume
table").

2.0 TEST
2.1 HARDWARE

2.1.1 MASTER

Special function

Tests the hardware of
the master.

2.1.2 DISPLAY

Special function

Tests the hardware of
the display.

Options

Module DIS

2.1.3

STATUS

Module

MW

Displays

ID-Number

and Status Bytes

2.2 CUR.OUTP.I

2.2.1

VALUE I

Value display

Displays the actual
value of the current
output.

Options 2

mA

4

mA

6

mA

8

mA

10

mA

12

mA

14

mA

16

mA

18

mA

20

mA

2.2.2

TEST

I

22

mA

2 mA

Output of selected
value to the current
output.

IMPORTANT !!! With
safety inquiry because
of direct access to the
current output !!!

(Exi = min. 3.6 mA)