Function (Fct.)

Enter range

Default value

Description

3.3.4 SCALE 20 mA

Enter
-200.00 ... +200.00
[m]
0.00 ... 99999.99
[m3]
0 ... 100
[Refl.]

10.00 m *
10.00 m3
100

Input of the full-scale
range for output to the
current output.
(Input is dependent on
the selected function
of the current output.
The values for level
and distance include
the tank bottom and
reference offset,
resp.).

Options 1200

Bd.

2400

Bd.

4800

Bd.

9600

Bd.

19200

Bd.

3.3.5

BAUDRATE

38400

Bd.

19200 Bd. *

Select the baud rate
for the Communication
interface (not relevant
to HART

via current

output).
(For Fct. 3.3.7 =
PROFIBUS-PA or
F.FOUND.: deviating
options.)

3.3.6 ADDRESS

Enter

0 ... 255

0

Input of the device
address for
Communication.
(For Fct. 3.3.7 =
PROFIBUS-PA or
F.FOUND.: deviating
input range)

Options HART

®

(MODBUS)
(PROFIBUS-

PA)

3.3.7

PROTOCOL

(F.FOUND.)

HART

®

Select

the

Communications
protocol. (only when
appropriate hardware
provided

3.4 USER DATA

Options GB/USA
D
F
I
E
P

3.4.1

LANGUAGE

S

GB/USA *

Select language to be
used in the display
(English, German,
French, Italian,
Spanish, Portuguese,
Swedish)

Options NO

3.4.2 ENTRY CODE1

YES

NO

Switch the access
lockout for the
configuration menu
on/off.

3.4.3 CODE 1

Enter code

RRREEEUUU

Input of the Entry
Code.

3.4.4 LOCATION

Text

BM70-00

Input of a max. 8-
character device
identifier.

3.5 APPLICAT.

3.5.1 AUTO TANKH.

Special function

Automatic
determination of the
tank height