6

OPERATION

70

OPTIWAVE 6300 C

www.krohne.com

03/2014 - 4000547004 - HB OPTIWAVE 6300 R04 en

Peak and spectrum

Spectrum quality is bad

W

The quality of the spectrum is

poor. If this message is

temporarily shown, this will

not affect the performance of

the device. If this message is

continuously shown, the

measured values can be

incorrect. The error message

"Measurement is old" will

then be displayed. Possible

causes are internal silo

elements.

Check the device, silo and the

process. Reconfigure the

device and record a new

empty spectrum. Follow the

instructions on page 62. If

necessary, contact the

supplier.

Empty spectrum is invalid

W

The Empty Spectrum stored

in the device does not agree

with the installation. If you

change the device

configuration (application

type, installation type, tank

height etc.), this message

will be displayed. The

recorded empty spectrum will

not be used by the device

while this error message is

displayed.

Check the device, silo and the

process. Reconfigure the

device and record a new

empty spectrum. Follow the

instructions on page 62. If

necessary, contact the

supplier.

Plausible peak is not

available

W

The signal peak is not found

within the measuring window

that filters the signals

received by the antenna. The

measurement is not correct.

The device will automatically

increase this window to find

the correct signal.

Check the device, silo and the

process. Reconfigure the

device and record a new

empty spectrum. Follow the

instructions on page 62. If

necessary, contact the

supplier.

Software error

Unable to load DSP firmware

E

The DSP Firmware did not

download correctly to the

DSP board.

Restart the device. If the

problem continues, contact

the supplier or replace the

electronics block. For more

data, refer to

Replacement of

the complete electronic

module

on page 74.

Error Message

Error

code

Description

Corrective action