Operation – KROHNE OPTIWAVE 6300C EN User Manual
Page 48

6
OPERATION
48
OPTIWAVE 6300 C
www.krohne.com
03/2014 - 4000547004 - HB OPTIWAVE 6300 R04 en
4
Distance
If the silo is partially filled, type
in a distance shorter than that
between the flange and the
tank contents.
min-max:
0…tank height
10 m /
32.808 ft
5
Do you want to
consider Average
or Maximum value
for recording?
Use the average value for silos
which contain fixed objects
only. Use the maximum value
for silos which contain many
objects or moving objects.
Average, Maximum
Average
6
Empty spect.
recording is in
progress
…
…
…
7
Empty spectrum
graph
…
…
…
8
Do you want to
save the
spectrum?
If you save this data, the device
will use it when it measures
the silo contents.
Save, Cancel
3
Save
A.1.4
A.1.4
A.1.4
A.1.4
Conversion
Conversion
Conversion
Conversion
Follow this procedure to set
Follow this procedure to set
Follow this procedure to set
Follow this procedure to set
the device up to display
the device up to display
the device up to display
the device up to display
readings in volume, mass or
readings in volume, mass or
readings in volume, mass or
readings in volume, mass or
user-defined units.
user-defined units.
user-defined units.
user-defined units.
Sub-
menu
Conversion
submenu [Volume]
[Volume]
[Volume]
[Volume]
1
Do you want to use
free unit?
Select "No".
Yes, No
No
2
Table Length Unit
m, cm, mm, inch, ft, Free
Unit
m
3
Please select
Volume / Mass
Select "Volume".
Volume
4
Tank Shape
This sub-procedure uses the
information given here to find
the volume. You have to type in
the silo shape, height, width
and length.
...
...
5
Conversion Unit
The displayed unit in operator
mode.
m3, L, US gal, GB gal, ft3,
bbl
m3
6
Volume Table
A table that converts product
level to product volume.
Push[
] or [
] to select a line
and push [>>>>] to change values
automatically supplied by the
device.
Sub-
menu
Conversion
submenu [Mass]
[Mass]
[Mass]
[Mass]
–
1
Do you want to use
free unit?
Select "No".
Yes, No
No
2
Table Length Unit
m, cm, mm, inch, ft, Free
Unit
m
3
Please select
Volume / Mass
Select "Mass".
Mass
4
Do you want to use
the density of the
product?
Yes, No
Yes
5
Product Density
min-max:
0…20000 kg/m3
0
Menu
No.
Step
Function
Function description
Selection list
Default