beautypg.com

Figure 26 n7 dc power wiring with transceiver – Detcon X40-32-N7 User Manual

Page 33

background image

Model X40

Model X40 Instruction Manual

Rev. 3.3

Page 27 of 64

CAUTION

The cable used to connect to the terminals of the X40-32-N7 must be rated for a
minimum of 105ºC.

2. Install AC power and I/O connections when the N7 is supplied with a J-Box and an AC/DC

converter. Connect 100-240VAC input wiring to the J3 connector (labeled AC IN) of the converter
board.

NOTE

The terminals on the J3 connector are labeled N (neutral), L (line power) and E (earth
ground).

NOTE

An optional Transient Protection board is available from Detcon for use with external DC
Supply. When using external DC power to power the controller the input power must be
11.5-30VDC.

3. After applying AC to the unit observe that the controller display starts and the unit will go through

the boot-up sequence (Section 3.12).

DC Operated Units

1. For units that will be wired to an external power source connect the external power to the Transient

Protection PCA ‘+’ and ‘-‘ terminals. Voltage input must be between 11.5VDC and 30VDC.

Wiring to

RXT-320

Transceiver

Customer Supplied Wiring

VDC(+)

VDC(-)

VDC(+)

VDC(-)

A

B

11.5~30VDC

V

D

C

(+

)

V

D

C

(-

)

A

B

Wiring to

X40-32-N7 Controller

J7 Connector

Figure 27 N7 DC Power Wiring with Transceiver

NOTE

An optional Transient Protection board is available from Detcon for use with external DC
Supply. When using external DC power to power the controller the input power must be
11.5-30VDC.

2. After applying power to the unit observe that the controller display starts and the unit will go

through the boot-up sequence (Section 3.12).