1.10.3 RL4/Alarm Stations Group
Hardwired RL4 Module
RMXX> ‘Status’
XX – represents the RL4 Modbus slave address.
‘Status’ – Status message of the RL4 module.
COMM ERR = Not communicating with module.
RL4 MODULE = Communicating with module.
Wireless Alarm Stations
ASXX ‘Status’ YYY%
XX – represents the alarm station Modbus slave address.
‘Status’ – Status message of the alarm station.
OFFLINE = Not communicating.
DC POWER = Communicating; line powered.
BATT ERR = Communicating; cannot read smart battery pack.
LOW BATT = Communicating; smart battery state of charge below the set threshold.
0 – 100% = Communicating; current state of charge of the smart battery pack.
YYY% - represents the link quality of the alarm station.
1.10.4 AO-4 Group
AMXX> ‘Status’
XX – represents the AO-4 module Modbus slave address
‘Status’ – Status message of the AO - 4 module
COMM ERR = Not communicating with module
AO-4 MODULE = Communicating with module
1.11 Menu Function
The X40 controller setup is accomplished through the Main Menu and consists of seven menu items:
1. Auto Configure System
2. Setup Channel Data
3. Set Channel Alarms
4. Set Relay Function
5. Inhibit & Alarm Test Mode
6. System Diagnostics
7. Time and Date
8. View TWA & Peak
Auto Configure System
The Auto Configure System automatically configures the X40 controller when other Detcon devices are
installed as part of the control system. When activated, the controller searches for Detcon serial sensors,
RL-4 modules/alarm stations, AO-4 modules and wireless radio modules.
Setup Channel Data
Setup Channel Data displays the Modbus ID, device type, range, and gas type for each channel. The
assigned RL4 bank and number of analog inputs (for channels using an RXT-320) is also displayed. Only
the gas type can be changed by the user. No other values on this screen can be changed.