beautypg.com

Math channel > expression, alarm, Math channel > constant, Math channel > tlog, rolling average – Yokogawa Removable Chassis DX1000N User Manual

Page 70: Math channel > color, Math channel > zone, scale, Math channel > bar graph

background image

68

IM 04L41B01-02E

Math channel > Expression, Alarm

Setup Item

Selectable Range or Selections

Default Value

Setting

First-CH, Last-CH

Channel number

101

Math On/Off
Calculation expression
Span Lower
Span Upper
Unit

On/Off
120 characters or less
–9999999 to 99999999, decimal position: 0 to 4
–9999999 to 99999999, decimal position: 0 to 4
6 characters or less

Off

–200.00
200.00

Math alarm

1, 2, 3, 4
Type
Value
Relay
No.

Detect

On/Off
H:High/L:Low/T:delayH/t:delayL
Numerical value
On/Off
I01/.../I06 (Depends on the option.)
S01/S02/S03/.../S29/S30
On/Off

Off
H

Off
I01

On

Math channel > Constant

Setup Item

Selectable Range or Selections

Default Value

Setting

Number of constant

K01 to K60

K01

Value

–9.9999E+29 to –1.0000E–30, 0,

1.0000E–30 to –9.9999E+29

1

Math channel > Tag, Memory, Delay

Setup Item

Selectable Range or Selections

Default Value

Setting

First-CH, Last-CH

Channel number

101

Tag > Comment

*2

32 characters or less

Tag > No.

*2

16 characters or less

Memory sample > On/Off

On/Off

On

Alarm delay > Time

1 to 3600

10

Math channel > TLOG, Rolling average

Setup Item

Selectable Range or Selections

Default Value

Setting

First-CH, Last-CH

Channel number

101

TLOG > Timer type

*2

TLOG > Timer No.

TLOG > Sum scale
TLOG > Reset

Timer/Match T
1/2/3/4

1/2/3/.../11/12 (on models with the /BT2 multi

batch option)

*2

Off, /s, /min, /h
On/Off

Timer
1

Off
Off

Rolling average > On/Off
Rolling average > Interval

Rolling average > Number of samples

On/Off
1s/2s/3s/4s/5s/6s/10s/12s/15s/20s/30s/

1min/2min/3min/4min/5min/6min/10min/12min/

15min/20min/30min/1h
1 to 1500

Off
10s

1

Math channel > Color

Setup items and values are the same as those for measurement channels, except the channel numbers.

Math channel > Zone, Scale

Setup items and values are the same as those for measurement channels, except the channel numbers.

Math channel > Bar graph

Setup items and values are the same as those for measurement channels, except the channel numbers.

Setup Items and Default Values

This manual is related to the following products: