background image

4

IM 04L41B01-02E

Wiring Screw Terminals

+

+

DC voltage input

TC input

DC voltage input/DI (ON/OFF) input

RTD input

DC current input

DC current input

Shunt resistor
Example: For 4 to 20 mA input, use a

shunt resistor of 250 Ω

+

+

+

A

B

b

Lead wire resistance per wire of
10 Ω or less. Make the resistance
of the three wires equal.

A

b

B

Compensating leadwire

±0.1%.

Wiring Clamped Terminals

CAUTION

As of August, 2007, the direction of the terminal blocks for the clamp input terminals

(/H2 option) has changed. To use clamp input terminal blocks wired for use with

previous YOKOGAWA recorders, rewire them to match the DX.

Remove the terminal block

Hold both ends of the terminal

block and pull straight.

Input signal wire

First, loosen the screw at the front using a flat-blade

screwdriver. Insert the input signal wire into the slit on the

left side of the terminal block, and fasten the screw at the front.

Recommended wire size

0.08 to 1.5 mm

2

(AWG 28 to 16)

Recommended

length of stripped

wire: 7 mm

Connect the wires

Flat-blade

screwdriver

Connect the terminal block

Hold both ends of the terminal block,

align with the connector on the DX

side, and push the terminal block into

the connector.

Note

RTD input terminals A and B are isolated on each channel. Terminal b is shorted internally

across all channels. However, terminal b is also isolated on each channel on models with the

/N1 option (Cu10, Cu25 RTD input/3 leg isolated RTD) and /N2 option (3 leg isolated RTD).

Installation and Wiring